Control Mode
Vector Control
Type of Motor
Encoder
Features
Volts / Hertz control
mode (V/Hz)
No vector control
Induction - usually mu‐
liple connected in par‐
allel
Without encoder
• No fast bypass
• No spinning load
Closed loop vector con‐
trol mode (CLVC)
Vector control
Induction
With encoder
• Fast bypass option
• Spinning load op‐
tion
Closed synchronous
motor control mode
(CSMC)
Vector control
Synchronous
With encoder
• Fast bypass option
• Spinning load op‐
tion
Permanent magnet mo‐
tor control mode (PMM)
Vector control
Permanent magnet
motor
Without encoder
• Fast bypass option
• No spinning load
• High starting tor‐
que enabled auto‐
matically
Synchronous motor
brushless DC exciter
mode (SMDC)
Vector control
Synchronous with DC
exciter
Without encoder
• No fast bypass
• No spinning load
4.7.4
Open Loop Vector Control (OLVC)
Open loop vector control (OLVC) is used for most applications with single induction motors. In
this mode, the control estimates motor slip as a function of load torque, and provides a
performance that matches a vector controlled drive with speed sensor/transducer above a
certain minimum speed. With the correct motor parameters, the control can provide good
performance even at 1% of rated speed.
With this mode, speed feedback is synthesized from the stator frequency and the estimated
motor slip, and slip compensation is automatic.
In this control mode, if spinning load is selected, the drive begins by scanning the frequency
range to detect the speed of the rotating motor. Once the drive has completed the scan or if the
feature is disabled, the drive goes into magnetizing state. During this state, the drive ramps the
motor flux to its commanded value at the specified flux ramp rate. Only when the flux feedback
is within 90% of the commanded flux, the drive changes to the run state. Once in run state, the
drive increases the speed to the desired value. All motor and drive parameters are required for
this mode of operation. Default values for the control loop gains are sufficient for most
applications.
Control Description
4.7 Control Modes
Control Manual
50
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...