– No input protection fault
Note
Cells in bypass
If any cells are in bypass prior to losing MV, their respective bypass contactor is opened
since the bypass contactor power supply is energized by one phase of the MV input.
During the subsequent pre-charge, if the cell is detected as faulted, pre-charge will pause
indefinitely until a manual drive reset is activated.
Pre-charge will then proceed and the detected faulted cell will be bypassed after pre-
charge is complete.
Setting
StartCellPrecharge_O
to true initiates the pre-charge sequence. Pre-charge will
not initiate if
DriveReadyToPrecharge_I
is not true, or any of the above conditions are not
met.
8.17.15.6
Type 5 (Open) Pre-charge
Type 5 pre-charge controls the main contactor, M1 and uses three pre-charge contactors M2,
M3, and M4. It is designed so that M1 will not close until after M4 opens. This designates type
5 pre-charge as a break-before-make, or open pre-charge type.
Type 5 pre-charge can be implemented only with the user I/O board due to the dedicated I/O
controlled directly through the NXGpro code.
Note
Pre-charge fault correction
On any pre-charge fault, you must examine the event log for the cause, and correct the problem
before proceeding to another attempt.
Note
Pre-charge benefit
The benefit of pre-charge is to limit transformer in-rush.
Advanced Operating Functions
8.17 Synchronous Transfer
Control Manual
276
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...