Fault handling
To reset a fault manually, use the [FAULT RESET] key on the keypad. Return the drive to the run
condition by performing manual start or by forcing the
RunRequest_I
equal to "true".
Certain faults can be reset automatically if enabled by the auto fault reset enable (7120). Refer
to Table Auto resettable faults, for a list of auto resettable faults. These are fixed and not
adjustable. If reset is successful, the drive will return to the run state automatically only if the
RunRequest_I
is maintained at the value "true". The [FAULT RESET] key of the keypad is also
used to acknowledge alarms.
Table 7-4
Auto resettable faults
Over Speed Fault
Keypad Communication
Encoder Loss
Under Load Fault
Network 1 Communication
Loss of Signal 1 to 24
Output Ground Fault
Network 2 Communication
Int AI1 to AI12 Loss of Signal
IOC
Motor Over Volt Fault
Loss Of Drive Enable
Menu Initialization
Back EMF Timeout
Motor Pull-out Fault
Medium voltage low Flt
Failed To Magnetize
SMDC PLL Start-up Fault
Line Over Voltage Fault
Loss Of Field Current
SM Pole Slip
Operating the Control
7.15 Faults and Alarms
Control Manual
232
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...