7.10
Drive Output Torque Limiting
The drive uses measured voltages and currents to implement rollback conditions. Under one or
more of these conditions, the drive will continue to operate, but at a lower output torque or
current level. An output torque limit will force the motor and the drive to go into speed rollback,
during which speed is reduced until the torque demanded by the load falls below the torque
limit. Rollbacks are triggered by various conditions and are described in the following sections.
7.10.1
Input Under-Voltage Rollback
When the input line voltage drops below 90% of its rated value, the drive limits the amount of
power, and thus torque, that can be delivered to the load. The maximum allowable drive power
as a function of line voltage is shown in the figure below. At 66% input voltage, the maximum
drive power is limited to 50%, and is quickly reduced to a slightly negative value at 65%. This is
the regenerative limit. This limit forces the drive to absorb power from the motor and maintain
the cell DC-bus voltages, in case the input voltage recovers during MV ride-through. The limit is
implemented as an inverse function of speed to maintain constant power flow to the cell DC-
bus.
A regulator is implemented to match the maximum drive power (P
max
) to the actual power
flowing into the drive. The output of this regulator sets the output torque limit.
5HJHQ/LPLW
(
0D[
UPV
3
PD[
Figure 7-21
Drive Power (P
max
) as Function of Input Voltage Magnitude (E
d
)
Parameters for Proportional and Integral Gains of the Regulator
Refer to Input Protect Menu (7000) in Section Options for Drive Protect Menu (7) of
Chapter Parameter Assignment / Addressing for parameters associated with this function.
• Undervoltage prop gain (7060) represents the proportional gain of this regulator.
• Undervoltage integ gain (7070) represents the integral gain of this regulator.
• An under-voltage rollback condition is indicated by the drive, by displaying UVLT on the
keypad and in the ToolSuite.
Operating the Control
7.10 Drive Output Torque Limiting
Control Manual
212
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...