7.7
Motor Thermal Overload Protection
The control provides the motor thermal overload (TOL) protection feature for motor protection.
TOL prevents the motor from being subjected to excessive temperatures that could lead to
overheating.
This software model does not measure the motor temperature directly; it estimates the
temperature from available data and is dependent on the entered parameters being accurate.
The software model has no data about the ambient temperature at the location of the motor. For
critical applications, you must use a direct measurement method such as Resistance
Temperature Detectors (RTD) inside the motor.
Setting TOL Parameters
Refer to Limits Menu (1120) in Section Options for Motor Menu (1) of Chapter Parameter
Assignment / Addressing for parameters to set up TOL protection of the motor. The associated
parameters are:
• Overload select (1130)
• Overload pending (1139)
• Overload (1140)
• Overload timeout (1150)
• Speed derate curve (1151)
• Maximum motor inertia (1159)
You may select one of four options for the overload select parameter for motor protection.
Constant Mode
The first option, "constant", is based on the current flowing into the motor. A Motor Thermal
Overload Alarm 1 of an impending overload fault is issued as a warning, when the motor current
exceeds the overload pending parameter. A Motor Thermal Overload Alarm 2 is issued and a
thermal trip timer is started, when the drive current exceeds the overload setting. If this
condition is present for a period greater than the time set in the Overload timeout parameter,
the drive will trip and annunciate the event as Motor Thermal Overload Fault.
Note
Displaying motor thermal overload alarms
Alarms 1 and 2 must be enabled through the SOP for the drive to display these conditions.
Inverse time Modes
The second and third options, "straight inverse time" and "inverse time with speed derating", use
a software motor thermal model to determine motor temperature.
Operating the Control
7.7 Motor Thermal Overload Protection
Control Manual
194
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...