2.7.5
Requirements for the circuit breaker provided by the customer
The circuit breaker on the primary side of the input transformer on the plant side belongs to the
safety system of the drive. If a fault occurs inside the drive, the energy that is effective at the
fault location must be limited. This is realized as a result of the inductance of the incoming
transformer, which limits the rate-of-rise and magnitude of the current and the circuit breaker
that trips as quickly as possible.
WARNING
High voltages and arcs
Circuit breakers are safety components. Connecting or setting the circuit breaker incorrectly
can result in death, serious injury, or material damage.
Connect the circuit breakers correctly. Select the system values that match the drive.
To ensure adequate drive protection, the circuit breaker provided by the customer must fulfill
the following requirements:
● The total opening time of the circuit breaker – from the command to actually opening – must
not be more than 80 ms. It is not permissible that the opening time, specified in the technical
documentation of the circuit breaker manufacturer, exceeds 80 ms. The drive monitors the
total opening time.
● The drive monitors the TRIP coils (shunt releases) for wire breakage and failure of the
control voltage in the switchgear installation.
● The circuit breaker must be equipped with an undervoltage tripping function. The
undervoltage trip unit (low-voltage coil) is controlled via the tripping circuit in which the
"undervoltage trip unit" of the drive must also be integrated. The auxiliary voltage from the
switchgear (this is a reliable supply) is used as the supply.
● Avoid additional delay times when controlling the circuit breaker. All commands from the
drive to the circuit breaker must act directly without intervention of coupling relays.
● A feedback signal must be available for each of the circuit breaker states CLOSED and
OPEN. The feedback signals must not be delayed. Do not use any coupling relays.
● An additional, independently operating overcurrent protection for the circuit breaker must be
provided on the plant side (transformer and cable protection).
● The circuit breaker is activated and enabled by the drive closed-loop controller. Under no
circumstances should you close the circuit breaker by external mechanical or electrical
means. A mechanical interlock of the manual ON command at the circuit breaker prevents
destruction of the drive as a result of an uncoordinated switch-on operation.
2.8
Residual risks
According to the EU machinery directive, machine manufacturers / plant operators must
conduct a risk assessment of their machine. Plant operators must conduct a risk assessment
of their plant. In particular, pay attention to Annex 1 "General Principles" of the EU machinery
directive.
Safety instructions
2.8 Residual risks
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
21
Содержание SINAMICS PERFECT HARMONY GH150 6SL3826
Страница 2: ...19 06 2020 09 25 V14 00 ...
Страница 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Страница 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Страница 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Страница 132: ...Additional documents SINAMICS PERFECT HARMONY GH150 6SL3826 132 Operating Instructions 05 2020 ...
Страница 135: ......
Страница 136: ...Further Information www siemens com LDA Siemens AG Large Drives Applications Vogelweiherstr 1 15 90441 NÜRNBERG GERMANY ...