9.7.4
Replacing the current transformer
Removing the current transformer
1. Remove the power cables which are screwed to the busbar.
2. Loosen the screw at the busbar and remove the measuring resistor.
Ensure that the cable of the measuring resistor is not damaged.
Figure 9-7
Replacing the current transformer
3. Loosen and remove the screw at the busbar.
4. Remove the connecting cable between the current transformer and the AVT combination
module. To do this, loosen the nuts on the side of the current transformer and remove the
cable.
5. Release the 4 screws that fasten the current transformer to the busbar.
6. Loosen the screw and the three screws that connect the busbar to the fixing plate. When
doing so, keep a firm grip on the busbar to ensure it does not fall.
7. Pull the busbar out to the front.
When doing so, be aware of the cables connected to the second current transformer.
8. Remove the current transformer from the bottom.
Maintenance
9.7 Repair
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
107
Содержание SINAMICS PERFECT HARMONY GH150 6SL3826
Страница 2: ...19 06 2020 09 25 V14 00 ...
Страница 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Страница 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Страница 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Страница 132: ...Additional documents SINAMICS PERFECT HARMONY GH150 6SL3826 132 Operating Instructions 05 2020 ...
Страница 135: ......
Страница 136: ...Further Information www siemens com LDA Siemens AG Large Drives Applications Vogelweiherstr 1 15 90441 NÜRNBERG GERMANY ...