Connecting the motor to the dv/dt filter
Figure 3-11 Connecting the motor to the dv/dt filter
Restrictions when using the dv/dt filter
● The drive may be operated only with following maximum currents:
– 4 kA drive: 1680 A (without filter 1750 A)
– 5 kA drive: 1780 A (without filter 1850 A)
● The pulse frequency of the drive must not exceed 200 Hz.
● The permissible output frequency of the drive must not exceed 100 Hz.
● The following line length between the filter output and the motor is permitted with shielded
cables (cable cross-section 185 mm
2
):
– 200 m when six parallel cables are used
– 400 m when three parallel cables are used
● The re-cooling unit requires 10 liter more flow
Description
3.6 Description of options
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
61
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......