6.4
Electrical requirements
Table 6-1
Dimensioning cables
Object
Length
Cable length (motor side)
100 m with one or two parallel ca‐
bles;
80 m with three parallel cables
Cables must be shielded
1000 m with output reactor (op‐
tion L08) or sine-wave filter (op‐
tion Y15)
Capacitance per unit length max.
0.45 µF/km
Cable length (line side)
300 m
Table 6-2
Cable cross-sections
Object
Cross-section
Comments
Power cable
Max. 240 mm
2
Two per terminal (Basic Line Module)
Three per terminal (Motor Module)
Cabinet protective conductor
Max. 120 mm²
-
See also
6.5
Connection
6.5.1
Manually unlocking power-unit doors
To ensure operator protection, the drive is equipped with an electromechanical door
interlocking system. The doors cannot be opened until the make-proof grounding switch has
been closed. In the event of a complete voltage failure including failure of the auxiliary voltage,
the doors cannot be released via the grounding switch.
Because the drive is not yet connected, the doors are locked electromechanically. In order to
facilitate assembly and installation of the drive, the doors can be opened manually.
See also
Electrical connection
6.4 Electrical requirements
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
107
Содержание SINAMICS GM150
Страница 2: ...20 04 2017 13 25 V27 00 ...
Страница 16: ...Table of contents SINAMICS GM150 6SL3815 2LN41 4AA2 16 Operating Instructions 04 2017 ...
Страница 18: ...Introduction 1 1 About these instructions SINAMICS GM150 6SL3815 2LN41 4AA2 18 Operating Instructions 04 2017 ...
Страница 72: ...Description 3 6 Description of options SINAMICS GM150 6SL3815 2LN41 4AA2 72 Operating Instructions 04 2017 ...
Страница 192: ...Operation 8 5 Fault and system messages SINAMICS GM150 6SL3815 2LN41 4AA2 192 Operating Instructions 04 2017 ...
Страница 228: ...Spare parts SINAMICS GM150 6SL3815 2LN41 4AA2 228 Operating Instructions 04 2017 ...
Страница 232: ...Service Support SINAMICS GM150 6SL3815 2LN41 4AA2 232 Operating Instructions 04 2017 ...
Страница 256: ...Index SINAMICS GM150 6SL3815 2LN41 4AA2 256 Operating Instructions 04 2017 ...
Страница 257: ......