Use the "NetTool" supplied by HMS Industrial Networks to configure PROFIBUS. The NetTool
is not included in the scope of supply.
3.5.22
Optical link module (option G74)
The transition from PROFIBUS to a fiber-optic cable is implemented using the Optical Link
Module (OLM).
3.5.23
Diagnostics module PADU8-M (option G76)
In addition to the standard PROFIBUS connection for process control, this diagnostics module
also allows the exchange of signals via digital and analog inputs and outputs. The signals are
transmitted as isolated signals.
3.5.24
Electronic power supply with wide-range power supply unit 1 AC 93 - 253 V, or DC
88 - 360 V (option K71)
The redundant electronics power supply guarantees the internal power supply on practically
any supply voltage and even when there are large voltage fluctuations. The possible voltage
range is 1-ph 93–253 V AC (50/60 Hz) 20 A or 88–360 V DC 20 A. The internal power supply
for the power unit is also derived from the internal power supply of the power unit.
3.5.25
Inductive cable attenuation (option L05)
The inductive cable damping is required for high cable capacities at the converter output. High
cable capacities at the converter output occur especially for long cable connections.
The inductive cable damping initially limits the commutation, i.e. when discharging system
capacities, the rate of current rise dI/dt in the thyristors. For this purpose, dI/dt reactors are
installed in the motor-side connection busbars.
If necessary, dI/dt reactors are also installed in the line-side connection busbars.
Description
3.5 Options
SINAMICS GL150 6SL38555UN113KA0Z
54
Operating Instructions Rev.201910281450 EXAMPLE
Содержание SINAMICS GL150
Страница 2: ...28 10 2019 14 50 V18 00 ...
Страница 60: ...Description 3 5 Options SINAMICS GL150 6SL38555UN113KA0Z 60 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 106: ...Commissioning SINAMICS GL150 6SL38555UN113KA0Z 106 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 150: ...Spare parts SINAMICS GL150 6SL38555UN113KA0Z 150 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 162: ...Index SINAMICS GL150 6SL38555UN113KA0Z 162 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 163: ......
Страница 166: ......
Страница 168: ......