Service life in the backup mode
> 1 year at 70° C; >1.5 years at 20° C
Service life in operation
> 2 years
Replacing the backup battery
1. Switch off the main circuit-breaker.
2. Open the cabinet.
3. Disconnect the 24 VDC power supply and communications line on the operator panel.
4. Open the cover of the battery compartment.
5. Remove the old battery.
6. Insert a new battery.
7. Close the cover of the battery compartment.
8. Reconnect the 24 VDC power supply and communications line.
9. Close the cabinet.
Note
To ensure that no data is lost during a battery replacement, it must be replaced within one
minute.
If the time is exceeded, the AOP settings and input screen texts are reloaded from the
CompactFlash card by a restart of the AOP with a connection to the drive.
Set the clock to the new time.
Figure 9-3
Replacing the backup battery
Note
Dispose of the battery in accordance with the applicable country-specific laws and regulations.
Set date and time
1. Using the "MENU" key, select the main menu of the AOP 30.
2. Using "F2", select the menu item "Commissioning/service". Confirm with "F5"
3. Using "F2", select the menu item "AOP30 settings". Confirm with "F5"
Maintenance
9.5 Maintenance
SINAMICS GL150 6SL38555UN113KA0Z
130
Operating Instructions Rev.201910281450 EXAMPLE
Содержание SINAMICS GL150
Страница 2: ...28 10 2019 14 50 V18 00 ...
Страница 60: ...Description 3 5 Options SINAMICS GL150 6SL38555UN113KA0Z 60 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 106: ...Commissioning SINAMICS GL150 6SL38555UN113KA0Z 106 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 150: ...Spare parts SINAMICS GL150 6SL38555UN113KA0Z 150 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 162: ...Index SINAMICS GL150 6SL38555UN113KA0Z 162 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 163: ......
Страница 166: ......
Страница 168: ......