6.13.2
Connecting the auxiliary voltage
Connect the auxiliary voltage (e.g. for SITOP) to the terminal block. The maximum cross-
section of the cables is 2.5 mm
2
. You will find detailed information in the terminal diagram or in
the circuit manual under "Technical specifications and drawings".
See also
Technical specifications and drawings (Page 155)
6.13.3
Connecting circuit breakers
To connect the circuit breaker, proceed as follows:
1. Disconnect the cabinet from the power supply.
2. Route the control cables into the cabinet from below.
3. Connect the shields of the control cables to the serrated bar. For additional information, see
Chapter "Using the equipotential bonding strip and shield bus (Page 95)".
4. Connect the control cables as specified in the circuit manual.
6.13.4
Connecting the encoder
Procedure
NOTICE
Damage caused by incorrectly connected external encoder
Components can be damaged if the external encoder is not connected or operated correctly.
● Only one measuring system can be connected to each sensor module. The sensor module
is wired internally to the customer terminal strip. For further information, see the circuit
manual.
To connect the encoder, proceed as follows:
1. The five safety rules must be observed.
2. Disconnect the cabinet from the power supply.
3. Route the cables from the encoder into the cabinet from below.
4. Route the cable further up into the cabinet until it reaches the customer terminal strips.
Electrical connection
6.13 Connecting the closed-loop control
SINAMICS GL150 6SL38555UN113KA0Z
100
Operating Instructions Rev.201910281450 EXAMPLE
Содержание SINAMICS GL150
Страница 2: ...28 10 2019 14 50 V18 00 ...
Страница 60: ...Description 3 5 Options SINAMICS GL150 6SL38555UN113KA0Z 60 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 106: ...Commissioning SINAMICS GL150 6SL38555UN113KA0Z 106 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 150: ...Spare parts SINAMICS GL150 6SL38555UN113KA0Z 150 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 162: ...Index SINAMICS GL150 6SL38555UN113KA0Z 162 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 163: ......
Страница 166: ......
Страница 168: ......