
Mechanical installation
3.3 Mounting
Converter cabinet units
42
Operating Instructions, 07/2016, A5E03347396A
3.3.1
Mechanical installation: checklist
Use the following checklist to guide you through the mechanical installation procedure for the
cabinet unit. Read the "Safety instructions" section at the start of these Operating
Instructions before you start working on the device.
Note
Checking the checklist
Check the boxes accordingly in the right-hand column if the activity applies to the cabinet
unit in your scope of supply. In the same way, check the boxes once you have finished the
installation procedure to confirm that the activities are complete.
Item Activity
Yes
Completed
1
Check the shipping and handling monitors prior to assembly. Refer to "Mechanical
installation/Assembly/Preparatory steps/Shipping and handling monitors".
2
The ambient conditions must be permissible. See "Technical specifications/General
technical specifications".
The enclosed units must be firmly attached using the anchor points provided (see
"Mechanical Installation/Assembly").
The cooling air can flow unobstructed.
3
The minimum ceiling height (for unhindered air outlet) specified in the Operating
Instructions must be observed. The cooling air supply must be not be obstructed
(refer to "Mechanical installation/Preparatory steps").
4
Transport units separately shipped must be connected to one another (refer to "Me-
chanical installation/Mechanical connection of transport units that are shipped sepa-
rately").
5
Components that are supplied separately for transport reasons (canopy or hood)
must be fitted (see "Mechanical installation/Fitting additional canopies (option M21)
or hoods (option M23, M43, M54)").
6
The clearance around an open door (escape route) specified in the applicable acci-
dent prevention guidelines must be observed.
3.3.2
Preparation
3.3.2.1
Requirements on the installation location
The cabinet units are designed for installation in closed, electrical operating areas in
compliance with EN 61800-5-1. A closed electrical operating area is a room or area
containing electrical equipment that can be accessed by trained personnel only. Access is
controlled by a door or other form of barrier that can be opened only by means of a key or
other tool. The room or area is also clearly marked with appropriate warning notices.
The operating areas must be dry and free of dust. The air supplied must not contain any
electrically conductive gas, vapors, or dust, which could impair operation. It may be
necessary to filter the air supplied to the room where the equipment is installed. If the air
contains dust, filter mats (option M54) can be installed in front of the ventilation grills of the
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......