Electrical installation
4.10 Other connections
Converter cabinet units
188
Operating Instructions, 07/2016, A5E03347396A
X150 P1/P2 PROFINET interface
Table 4- 67 X150 P1 and X150 P2 PROFINET
Pin
Signal name
Technical data
1
RXP
Receive data +
2
RXN
Receive data -
3
TXP
Transmit data +
4
Reserved, do not use
5
Reserved, do not use
6
TXN
Transmit data -
7
Reserved, do not use
8
Reserved, do not use
Connector type: RJ45 socket
Cable type: PROFINET
Note
Connection cables
The PROFINET interfaces support Auto MDI(X). It is therefore possible to use both
crossover and non-crossover cables to connect the devices.
For diagnostic purposes, the two PROFINET interfaces are each equipped with a green and
a yellow LED. These LEDs indicate the following status information:
Table 4- 68 LED states on the X150 P1/P2 PROFINET interface
LED
Color
State
Description
Link port
-
Off
Missing or faulty link
Green Continuous
light
10 or 100 Mbit link available
Activity
port
-
Off
No activity
Yellow Flashing
light
Data is being received or sent at port x
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......