Electrical installation
4.9 Signal connections
Converter cabinet units
114
Operating Instructions, 07/2016, A5E03347396A
X521: 2 analog inputs (differential inputs)
Table 4- 20 Terminal block X521
Terminal
Designation
1)
Technical data
1
AI 0+
The analog inputs can be toggled between current
and voltage input using switches S5.0 and S5.1.
As voltage input:
-10 ... +10 V; R
i
>
100 kΩ
Resolution: 11 bits + sign
As current input:
-20 ... +20 mA; R
i
= 250 kΩ
Resolution: 10 bits + sign
2
AI 0-
3
AI 1+
4
AI 1-
5
P10
Auxiliary voltage:
P10 = 10 V
N10 = -10 V
Continuously short-circuit proof
6
M
7
N10
8
M
Max. connectable cross-section: 1.5 mm²
1)
AI: analog input; P10/N10: auxiliary voltage, M: Ground reference
NOTICE
Damage or malfunctions through impermissible voltage values
If a current exceeding ±35 mA flows through the analog current input, then the component
could be destroyed.
The common mode range must not be violated in order to avoid incorrect analog-digital
conversion results.
•
The input voltage may only be in the range between -30 V and +30 V (destruction limit).
•
The common mode voltage may only be in the range between -10 V and +10 V (error
limit).
•
The back EMF at the auxiliary voltage connections may only be in the range between -
15 V and +15 V.
Note
The power supply for the analog inputs can be taken internally or from an external power
supply unit.
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......