4.2.5
Default setting of the interfaces
Overview
The function of most of the converter terminals can be set.
In order that you do not have to successively change terminal for terminal, several terminals
can be jointly set in the quick commissioning using default settings. Parameter p0015 in the
quick commissioning selects the appropriate default setting.
Table 4-7
Overview of default settings, Part 1/2
Default setting
Terminal
41
42
43
44
45
46
AI 0
Setpoint
Setpoint
Setpoint
Setpoint
Setpoint
Setpoint local
AI 1
-
PID actual value PID actual value PID actual value
-
Setpoint remote
AO 0
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1 Current actual
value
Current actual
value
Current actual
value
Current actual
value
Current actual
value
Current actual
value
DI 0
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2 local
DI 1
-
-
Service pump 1
Service pump 1 Fixed setpoint 1
ON/OFF2 re‐
mote
DI 2
-
-
Service pump 2
Service pump 2 Fixed setpoint 2
-
DI 3
-
-
-
Service pump 3 Fixed setpoint 3
-
DI 4
-
manual ↔ auto
manual ↔ auto
manual ↔ auto
-
local ↔ remote
DI 5
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
DO 0
Fault
Fault
Fault
Fault
Fault
Fault
DO 1
Operation
Operation
Operation
Pump 1
Operation
Operation
DO 2 Ready for opera‐
tion
Ready for opera‐
tion
Pump 1
Pump 2
Ready for opera‐
tion
Ready for opera‐
tion
DO 3
Alarm
Alarm
Pump 2
Pump 3
Alarm
Alarm
Table 4-8
Overview of default settings, Part 2/2
Default setting
Terminal
47
48
49
51
52
54
55
AI 0
-
-
-
-
Setpoint local
-
Setpoint local
AI 1
PID actual
value
PID actual
value
PID actual
value
-
-
-
-
AO 0 Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
DI 0
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2 lo‐
cal
ON/OFF2
ON/OFF2 lo‐
cal
Wiring
4.2 Control interfaces
SINAMICS G120XA converter
82
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......