Cause:
A consistency error was detected when activating the configuration (p8925) for the PROFINET interface. The currently set
configuration has not been activated.
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
Note:
DHCP: Dynamic Host Configuration Protocol
Remedy:
- check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925).
or
- reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
A50011 (F)
Ethernet/IP: configuration error
Reaction:
NONE
Acknowledge:
NONE
Cause:
An EtherNet/IP controller attempts to establish a connection using an incorrect configuring telegram.
The telegram length set in the controller does not match the parameterization in the drive device.
Remedy:
Check the set telegram length.
For p0922 not equal to 999, then the length of the selected telegram applies.
For p0922 = 999, the maximum interconnected PZD (r2067) applies.
See also: p0922 (PROFIdrive PZD telegram selection), r2067 (PZD maximum interconnected)
F52960
Cavitation protection failure
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Conditions exist for cavitation damage. Cavitation damage is damage caused to a pump in pumping systems when the fluid
is not flowing sufficiently. This can lead to heat build up and subsequent damage to the pump.
Remedy:
If cavitation is not occurring, reduce the cavitation threshold p29626, or increase the cavitation protection delay. Ensure
sensor feedback is working.
A52961
Cavitation protection warning
Reaction:
NONE
Acknowledge:
NONE
Cause:
Conditions for possible cavitation damage are detected.
Remedy:
See F52960.
A52962
Mpc operating time limit exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The continuous operating time of at least one motor has exceeded the limit.
Remedy:
Incease p29531 or set p29547 = 0.
A52963
Mpc PID deviation exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The PID deviation (p2273) has exceeded the threashold (p29544) and all motors are running except the motors under
service or locked.
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
825
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......