Acknowledge:
IMMEDIATELY
Cause:
The actual value for the free technology controller 1 has reached the limit.
The signal source for the actual value is set via connector input p11164.
Fault value (r0949, interpret decimal):
1: The actual value has reached the upper limit.
2: The actual value has reached the lower limit.
Remedy:
- adapt the limit settings to the actual value signal (p11167, p11168).
- check the scaling of the actual value signal.
- check the signal source setting for the actual value (p11164).
See also: p11164 (Free tec_ctrl 1 actual value signal source), p11167 (Free tec_ctrl 1 actual value upper limit), p11168
(Free tec_ctrl 1 actual value lower limit)
F07438 (A)
Free tec_ctrl 2 actual value limited
Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The actual value for the free technology controller 2 has reached the limit.
The signal source for the actual value is set via connector input p11264.
Fault value (r0949, interpret decimal):
1: The actual value has reached the upper limit.
2: The actual value has reached the lower limit.
Remedy:
- adapt the limit settings to the actual value signal (p11267, p11268).
- check the scaling of the actual value signal.
- check the signal source setting for the actual value (p11264).
See also: p11264 (Free tec_ctrl 2 actual value signal source), p11267 (Free tec_ctrl 2 actual value upper limit), p11268
(Free tec_ctrl 2 actual value lower limit)
A07444
PID autotuning is activated
Reaction:
NONE
Acknowledge:
NONE
Cause:
Automatic setting of the PID controller parameters (PID autotuning) was activated (p2350).
See also: p2350 (Enable PID autotuning)
Remedy:
Not necessary.
This alarm is automatically withdrawn after the PID autotuning has been completed.
F07445
PID autotuning canceled
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The PID autotuning was canceled as a result of an error.
Remedy:
- increase the offset.
- check system configuration.
A07530
Drive: Drive Data Set DDS not present
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected drive data set is not available (p0837 > p0180). The drive data set was not changed over.
See also: p0180, p0820, p0821, p0822, p0823, p0824, r0837
Remedy:
- select the existing drive data set.
- set up additional drive data sets.
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
SINAMICS G120XA converter
788
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......