p29596[0...n]
Deragging forward time / Derag fw time
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [s]
Max:
1000.00 [s]
Factory setting:
5.00 [s]
Description:
Defines the duration time at each forward speed for deragging.
p29597[0...n]
Deragging reverse time / Derag rev tim
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [s]
Max:
1000.00 [s]
Factory setting:
5.00 [s]
Description:
Defines the duration time at reverse speed for deragging.
p29598[0...n]
Number of deragging cycles / Derag cycs
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
1
Max:
999
Factory setting:
1
Description:
The number of the deragging cycle is repeated
p29610[0...n]
Pipe filling enable / PF En
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Enable the pipe filling function.
Value:
0:
The pipe filling function is disabled
1:
The pipe filling function is enabled
Note
The pipe filling function allows the inverter to fill an empty pipe slowly when the inverter works for the first time after each
power-up.
p29611[0...n]
Pipe filling mode / PF mode
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Selects the mode for pipe filling.
Value:
0:
The pipe is filled based on specified time
1:
The pipe is filled based on the actual pressure feedback
Parameters
7.3 Parameters
SINAMICS G120XA converter
716
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......