p29579[0...n]
CI: Ramp-down scaling input / Rdown scale input
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for scaling the ramp-down time of the ramp-function generator when p1139 is BICO to r29577.
When the dual ramp functionality is not enabled, p29579 will function.
p29580[0...n]
BI: Dual ramp enable / DuRamp En
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to enable the dual ramp function.
p29590[0...n]
Deragging mode / Derag mod
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Description:
Select the startup mode of deragging, if the condition is met with selected mode, deragging will perform when drive
start to run, then switch to user setpoint automatically.
Value:
0:
deragging disable
1:
enabled on first run after power up
2:
enabled on every run
3:
enabled by BI input
Note
If deragging is enabled (P29590 > 0), make sure that reverse direction is not inhibited, i.e. P1110 = 0;
If P29590=3, enable source is defined by P29591.
p29591[0...n]
BI: Deragging enable / Derag en
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
The source of deragging enable.
Note
Effective only if mode set as BI input(p29590=3).
Parameters
7.3 Parameters
SINAMICS G120XA converter
714
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......