p29539
Multi-pump control pump switchover enable / Mpc sw-over enab
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Enables the multi-pump control pump switchover function.
0: Pump switchover function inhibited
1: Pump switchover function enabled
Value:
0:
DISABLE_CYCLING
1:
ENABLE_CYCLING
Note
With pump switchover enabled, the inverter monitors the operation status of all running pumps.
If the continuous operating hours of the pump in inverter operation exceed the threshold, the inverter switches off the
pump and then switches in an idle pump to keep constant output power.
If the continuous operating hours of a pump in mains operation exceed the threshold, the inverter switches off the pump,
switches the inverter-controlled pump to mains operation, and switches in an idle pump to run in inverter operation to
keep constant output power.
p29540
Multi-pump control service mode enable / Mpc SerMode enab
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Enables the multi-pump control service mode.
0: Service mode inhibited
1: Service mode enabled
Value:
0:
disable
1:
enable
Note
When a pump is in service mode, the inverter locks the corresponding relay. Then you can perform troubleshooting of
this pump without interrupting the operation of other pumps.
p29542.0...3
CO/BO: Multi-pump control service mode interlock manually / Mpc ser_interl
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Sets the service mode manually.
When a motor fault is activated or a motor is not to run, user can set the corresponding bit to 1 to lock it.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
motor 1 locked
Yes
No
-
01
motor 2 locked
Yes
No
-
02
motor 3 locked
Yes
No
-
03
motor 4 locked
Yes
No
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
710
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......