1:
Inversion
CAUTION
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note
The correct setting can be determined as follows:
- inhibit free technology controller (p11200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the free technology controller).
- if the actual value increases with increasing motor speed, then deactivate inversion.
- if the actual value decreases with increasing motor speed, then activate inversion.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
p11264
CI: Free tec_ctrl 2 actual value signal source / Ftec2 act v s_s
Access level: 2
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the actual value of the free technology controller 2.
p11265
Free tec_ctrl 2 actual value smoothing time constant / Ftec2 act v T
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.00 [s]
Max:
60.00 [s]
Factory setting:
0.00 [s]
Description:
Sets the smoothing time constant (PT1) for the actual value of the free technology controller 2.
p11267
Free tec_ctrl 2 actual value upper limit / Ftec2 act v up lim
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: 9_4
Unit selection: p11226
Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the upper limit for the actual value signal of the free technology controller 2.
Dependency:
See also: p11264
p11268
Free tec_ctrl 2 actual value lower limit / Ftec2 act v lo lim
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: 9_4
Unit selection: p11226
Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
-100.00 [%]
Description:
Sets the lower limit for the actual value signal of the free technology controller 2.
Dependency:
See also: p11264
Parameters
7.3 Parameters
SINAMICS G120XA converter
702
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......