p11085
Free tec_ctrl 0 integral time / Ftec0 Tn
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.000 [s]
Max:
10000.000 [s]
Factory setting:
30.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the free technology controller 0.
Note
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
p11091
CO: Free tec_ctrl 0 limit maximum / Ftec0 lim max
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the maximum limit of the free technology controller 0.
Dependency:
See also: p11092
Note
The maximum limit must always be greater than the minimum limit (p11091 > p11092).
p11092
CO: Free tec_ctrl 0 limit minimum / Ftec0 lim min
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
0.00 [%]
Description:
Sets the minimum limit of the free technology controller 0.
Dependency:
See also: p11091
Note
The maximum limit must always be greater than the minimum limit (p11091 > p11092).
p11093
Free tec_ctrl 0 limit ramp-up/ramp-down time / Ftec0 lim r-u/r-dn
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.00 [s]
Max:
100.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11091, p11092) of the free technology
controller 0.
Dependency:
See also: p11091, p11092
Note
The ramp-up/ramp-down times are referred to 100%.
Parameters
7.3 Parameters
SINAMICS G120XA converter
690
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......