43:
ft wg
44:
m wg
45:
% r.h.
46:
g/kg
47:
ppm
48:
kg/cm²
Dependency:
Only units of parameters with unit group 9_2 can be changed over using this parameter.
See also: p11027
p11027
Free tec_ctrl 0 unit reference quantity / Ftec0 unit ref
Access level: 1
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.01
Max:
340.28235E36
Factory setting:
1.00
Description:
Sets the reference quantity for the unit of the parameters of the free technology controller 0.
When changing over using changeover parameter p11026 to absolute units, all of the parameters involved refer to the
reference quantity.
Dependency:
See also: p11026
p11028
Free tec_ctrl 0 sampling time / Ftec0 t_samp
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0
Max:
4
Factory setting:
2
Description:
Sets the sampling time for the free technology controller 0.
Value:
0:
Reserved
1:
128 ms
2:
256 ms
3:
512 ms
4:
1024 ms
r11049.0...11
CO/BO: Free tec_ctrl 0 status word / Ftec0 stat_word
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word of the free technology controller 0.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Deactivated
Yes
No
-
01
Limited
Yes
No
-
08
Actual value at the minimum
Yes
No
-
09
Actual value at the maximum
Yes
No
-
10
Output at the minimum
Yes
No
-
11
Output at the maximum
Yes
No
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
686
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......