Note
For bit 00 = 1:
The limit switch enables motion.
For example, this bit can be used for interconnection with binector input p0840 (ON/OFF1).
For bit 01 = 0:
The drive cannot be moved as a result of the limit switch function (e.g. as a result of the switching on inhibited).
For example, this bit can be used for interconnection with binector input p0848 (OFF3).
For bit 02 = 1:
The axis is at zero speed.
For bit 04 = 1:
The plus limit switch reached.
For bit 05 = 1:
The minus limit switch reached.
p3380
Forming activation/duration / Form act/duration
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.0 [h]
Max:
10.0 [h]
Factory setting:
0.0 [h]
Description:
Setting to activate the "DC link capacitor forming" function.
This value also defines the forming duration.
The function is deactivated with p3380 = 0.
Recommendation:
Recommended forming duration depending on the storage time:
1 - 2 years: p3380 = 1 hour
2 - 3 years: p3380 = 2 hours
>3 years: p3380 = 8 hours
Dependency:
The "DC link capacitor forming" function can only be executed when commissioning the power unit (p0010 = 2). The
function is automatically deactivated (p3380 = 0) once commissioning has been exited (p0010 = 0).
Procedure when forming:
1. Activate power unit commissioning (p0010 = 2).
2. Activate forming (p3380 > 0, value, see recommendation).
3. Switch on the drive unit (p0840 = 0/1 signal).
4. Wait for forming to be completed (r3381 = 0).
5. Exit power unit commissioning (p0010 = 0).
See also: r3381, r3382
See also: F07390, A07391
NOTICE
If drive units are not commissioned within 2 years after their original manufacture, then the DC link capacitors must be
reformed before use. If this is not done, then the units could be damaged in operation.
Note
The "DC link capacitor forming" function can only be activated online in the drive unit.
If switched off while forming is active, the remaining time (r3381) is lost, and forming must be repeated for the full
forming time. If the forming duration is changed, then forming starts again from the beginning.
r3381
Forming remaining time / Forming t_remain
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [h]
Max:
- [h]
Factory setting:
- [h]
Parameters
7.3 Parameters
SINAMICS G120XA converter
650
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......