p3230[0...n]
CI: Load monitoring speed actual value / Load monit n_act
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: p2000
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 8012, 8013
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the speed actual value of the load monitoring.
Dependency:
See also: r2169, p2181, p2192, p2193, p3231
See also: A07920, A07921, A07922, F07923, F07924, F07925
Note
The parameter is only effective for p2193 = 2.
p3231[0...n]
Load monitoring speed deviation / Load monit n_dev
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8013
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
150.00 [rpm]
Description:
Sets the permissible speed deviation during load monitoring (for p2193 = 2).
Dependency:
See also: r2169, p2181, p2193, p3230
See also: A07920, A07921, A07922, F07923, F07924, F07925
p3232[0...n]
BI: Load monitoring failure detection / Load_moni fail_det
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for detecting a failure.
Dependency:
See also: p2192, p2193
See also: F07936
Note
Monitoring is triggered with a 0 signal, as soon as the time in p2192 has expired.
p3233[0...n]
Torque actual value filter time constant / M_act_filt T
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
0 [ms]
Max:
1000000 [ms]
Factory setting:
100 [ms]
Description:
Sets the time constant for the PT1 element to smooth the torque actual value.
The smoothed torque actual value is compared with the threshold values and is only used for messages and signals.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
643
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......