
Dependency:
See also: p2310, p2311, p2312, p2313, p2314, r2316
Note
Kp adaptation is activated with p2252.7 = 1.
r2316
CO: Technology controller, Kp adaptation output / Kp adapt outp
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
-
Max:
-
Factory setting:
-
Description:
Display and connector output for the output signal of the adaption of proportional gain Kp for the technology controller.
Dependency:
See also: p2252, p2310, p2311, p2312, p2313, p2314, p2315
p2317
CI: Technology controller Tn adaptation input value signal source / Tn adapt inp s_src
Access level: 2
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the input value of the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2252, p2318, p2319, p2320, p2321, r2322
Note
Tn adaptation is activated with p2252.8 = 1.
p2318
Technology controller Tn adaptation lower value / Tn adapt lower val
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
3.000 [s]
Description:
Sets the lower value for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2319, p2320, p2321, r2322
CAUTION
The upper value must be set higher than the lower value (p2319 > p2318).
Note
Tn adaptation is activated with p2252.8 = 1.
p2319
Technology controller Tn adaptation upper value / Tn adapt upper val
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7959
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
10.000 [s]
Description:
Sets the upper value for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2318, p2320, p2321, r2322
CAUTION
The upper value must be set higher than the lower value (p2319 > p2318).
Parameters
7.3 Parameters
SINAMICS G120XA converter
622
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......