![Siemens SINAMICS G120XA Скачать руководство пользователя страница 580](http://html.mh-extra.com/html/siemens/sinamics-g120xa/sinamics-g120xa_operating-instructions-manual_381566580.webp)
p2105[0...n]
BI: 3rd acknowledge faults / 3rd acknowledge
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2546, 8060
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the third signal source to acknowledge faults.
Note
A fault acknowledgment is triggered with a 0/1 signal.
p2106[0...n]
BI: External fault 1 / External fault 1
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2546
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for external fault 1.
Dependency:
See also: F07860
Note
An external fault is triggered with a 1/0 signal.
p2107[0...n]
BI: External fault 2 / External fault 2
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2546
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for external fault 2.
Dependency:
See also: F07861
Note
An external fault is triggered with a 1/0 signal.
p2108[0...n]
BI: External fault 3 / External fault 3
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2546
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
See also: p3110, p3111, p3112
See also: F07862
Note
An external fault is triggered with a 1/0 signal.
Parameters
7.3 Parameters
SINAMICS G120XA converter
578
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......