Motor model changeover speed hysteresis encoderless operation / MotMod n_chgov hys
Access level: 3
Calculated: CALC_MOD_REG Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6730, 6731
Min:
0.0 [%]
Max:
95.0 [%]
Factory setting:
50.0 [%]
Description:
Sets the hysteresis for the changeover speed of the motor model for encoderless operation.
Dependency:
See also: p1755
Note
The parameter value refers to p1755.
Extremely small hystereses can have a negative impact on the stability in the changeover speed range, and very high
hystereses in the standstill range.
p1780[0...n]
Motor model adaptation configuration / MotMod adapt conf
CUG120XA_USS
(PM330)
Access level: 3
Calculated: CALC_MOD_CON Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 1000 0001 0100 bin
Description:
Sets the configuration for the adaptation circuit of the motor model.
Induction motor (ASM):
Rs, Lh and offset compensation.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Select motor model ASM Rs adaptation
Yes
No
-
02
Select motor model ASM Lh adaptation
Yes
No
-
04
Select motor model offset adaptation
Yes
No
-
07
Select T(valve) with Rs adaptation
Yes
No
-
10
Filter time combination current like current ctrl integral time Yes
No
-
11
Fast flying restart with voltage model for induction motor
Yes
No
-
Dependency:
In the U/f characteristic operating mode, only bit 7 and bit 11 are relevant.
For active motor model feedback (see p1784), the Lh adaptation is internally deactivated automatically.
Note
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is
deactivated and is instead taken into account in the motor model.
In order that the correction values of the Rs and Lh adaptation (selected using bit 0 ... bit 1) are correctly accepted when
changing over the drive data set, a dedicated motor number must be entered into p0826 for each different motor.
ASM: Induction motor
RESM: synchronous reluctance motor
p1800[0...n]
Pulse frequency setpoint / Pulse freq setp
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8021
Min:
0.500 [kHz]
Max:
16.000 [kHz]
Factory setting:
4.000 [kHz]
Description:
Sets the pulse frequency for the converter.
This parameter is pre-set to the rated converter value when the drive is first commissioned.
Dependency:
Minimum pulse frequency: p1800 >= 12 * p1082 * r0313 / 60
See also: p0230
Parameters
7.3 Parameters
SINAMICS G120XA converter
536
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......