p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
CUG120XA_USS
(PM330)
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1), T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
5400.000 [s]
Factory setting:
3.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Dependency:
The parameter is pre-assigned depending on the size of the power unit.
Note
This time can be exceeded if the DC link voltage reaches its maximum value.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
30.000 [s]
Factory setting:
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
30.000 [s]
Factory setting:
0.500 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
30.000 [s]
Factory setting:
0.000 [s]
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1138[0...n]
CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
See also: p1120
Note
The ramp-up time is set in p1120.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
485
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......