NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
The parameter is not used for synchronous motors (p0300 = 2).
p0356[0...n]
Motor stator leakage inductance / Mot L_stator leak.
Access level: 3
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00000 [mH]
Max:
1000.00000 [mH]
Factory setting:
0.00000 [mH]
Description:
Induction machine: sets the stator leakage inductance of the motor.
Synchronous motor: Sets the stator quadrature axis inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification
routine (p1910).
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
If the stator leakage inductance (p0356) for induction motors is changed outside the commissioning phase (p0010 >
0), the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then advised to
repeat the measurement for the saturation characteristic (p1960).
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is, therefore, ideal for a
low current.
For a controlled reluctance motor (p0300 = 6), this is the direct axis stator inductance at the rated operating point.
p0357[0...n]
Motor stator inductance d axis / Mot L_stator d
Access level: 3
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00000 [mH]
Max:
1000.00000 [mH]
Factory setting:
0.00000 [mH]
Description:
Sets the stator direct-axis inductance of the synchronous motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification
routine (p1910).
Note
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is ideal for a low current.
For a controlled reluctance motor (p0300 = 6), this is the direct axis stator inductance at the rated operating point.
p0358[0...n]
Motor rotor leakage inductance / Mot L_rot leak
Access level: 3
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: 6727
Min:
0.00000 [mH]
Max:
1000.00000 [mH]
Factory setting:
0.00000 [mH]
Description:
Sets the rotor/secondary section leakage inductance of the motor.
The value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910).
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
403
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......