r0313[0...n]
Motor pole pair number, actual (or calculated) / Mot PolePairNo act
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: 5300
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the number of motor pole pairs. The value is used for internal calculations.
r0313 = 1: 2-pole motor
r0313 = 2: 4-pole motor, etc.
Dependency:
For p0314 > 0, the entered value is displayed in r0313.
For p0314 = 0, the pole pair number (r0313) is automatically calculated from the rated power (p0307), rated frequency
(p0310) and rated speed (p0311).
See also: p0307, p0310, p0311
Note
For the automatic calculation, the pole pair number is set to the value of 2 if the rated speed or the rated frequency is
zero.
p0316[0...n]
Motor torque constant / Mot kT
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1), T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: 28_1
Unit selection: p0100
Function diagram: -
Min:
0.00 [Nm/A]
Max:
400.00 [Nm/A]
Factory setting:
0.00 [Nm/A]
Description:
Sets the torque constant of the synchronous motor.
p0316 = 0:
The torque constant is calculated from the motor data.
p0316 > 0:
The selected value is used as torque constant.
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
This parameter is not used for induction motors (p0300 = 1xx).
p0320[0...n]
Motor rated magnetizing current/short-circuit current / Mot I_mag_rated
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [Arms]
Max:
5000.000 [Arms]
Factory setting:
0.000 [Arms]
Description:
Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Parameters
7.3 Parameters
SINAMICS G120XA converter
394
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......