![Siemens SINAMICS G120XA Скачать руководство пользователя страница 378](http://html.mh-extra.com/html/siemens/sinamics-g120xa/sinamics-g120xa_operating-instructions-manual_381566378.webp)
Dependency:
If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
r0333, r0334, p0341, p0344, r1969).
See also: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0320, p0322, p0323, p0335,
p1800
Note
The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
p0124[0...n]
CU detection via LED / CU detection LED
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: T, U
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Identification of the Control Unit using an LED.
Note
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
p0133[0...n]
Motor configuration / Motor config
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: C2(1, 3)
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Configuration of the motor when commissioning the motor.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor connection type
Delta
Star
-
01
Motor 87 Hz operation
Yes
No
-
Dependency:
For standard induction motors (p0301 > 10000), bit 0 is automatically pre-assigned the connection type of the selected
data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
See also: p0304, p0305, p1082
Note
For bit 00:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically converted
to the selected connection type (star/delta).
For bit 01:
87 Hz operation is only possible in the delta connection type. When selected, the maximum speed p1082 is
automatically pre-assigned for a maximum output frequency of 87 Hz.
p0170
Number of Command Data Sets (CDS) / CDS count
Access level: 2
Calculated: -
Data type: Unsigned8
Can be changed: C2(15)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8560
Min:
2
Max:
4
Factory setting:
2
Description:
Sets the number of Command Data Sets (CDS).
Dependency:
See also: p0010, r3996
NOTICE
When the data sets are created, short-term communication interruptions may occur.
Parameters
7.3 Parameters
SINAMICS G120XA converter
376
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......