Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on the
power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
The following applies for p0096 = 1:
The motor type (p0300) synchronous or reluctance motor is not possible.
Note
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor data
identification as well as the setting of the operating mode and parameterization of the closed-loop control must be
appropriately adapted.
p0096
Application class / Appl_class
CUG120XA_USS
(PM330)
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6019
Min:
0
Max:
2
Factory setting:
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
Expert
2:
Dynamic Drive Control (DDC)
Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on the
power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
Note
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor data
identification as well as the setting of the operating mode and parameterization of the closed-loop control must be
appropriately adapted.
p0100
IEC/NEMA Standards / IEC/NEMA Standards
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1, 2)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
2
Factory setting:
0
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in [kW]
or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value:
0:
IEC (50 Hz line, SI units)
1:
NEMA (60 Hz line, US units)
2:
NEMA (60 Hz line, SI units)
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
375
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......