p0043
BI: Enable energy usage display / Enab energy usage
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to enable/reset the process energy display in r0042.
BI: p0043 = 1 signal:
The process energy display is enabled in r0042.
Dependency:
See also: r0042
p0045
Display values smoothing time constant / Disp_val T_smooth
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6799
Min:
0.00 [ms]
Max:
10000.00 [ms]
Factory setting:
4.00 [ms]
Description:
Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
r0046.0...31
CO/BO: Missing enable signal / Missing enable sig
Access level: 1
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2634
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for missing enable signals that are preventing the closed-loop drive control from being
commissioned.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
OFF1 enable missing
Yes
No
7954
01
OFF2 enable missing
Yes
No
-
02
OFF3 enable missing
Yes
No
-
03
Operation enable missing
Yes
No
-
04
DC braking enable missing
Yes
No
-
08
Safety enable missing
Yes
No
-
10
Ramp-function generator enable missing
Yes
No
-
11
Ramp-function generator start missing
Yes
No
-
12
Setpoint enable missing
Yes
No
-
16
OFF1 enable internal missing
Yes
No
-
17
OFF2 enable internal missing
Yes
No
-
18
OFF3 enable internal missing
Yes
No
-
19
Pulse enable internal missing
Yes
No
-
20
DC braking internal enable missing
Yes
No
-
21
Power unit enable missing
Yes
No
-
25
Function bypass active
Yes
No
-
26
Drive inactive or not operational
Yes
No
-
27
De-magnetizing not completed
Yes
No
-
30
Speed controller inhibited
Yes
No
-
31
Jog setpoint active
Yes
No
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
361
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......