6.7.6.4
Torque monitoring
Function description
In applications with fans, pumps or compressors with the flow characteristic, the torque follows
the speed according to a specific characteristic. An insufficient torque for fans indicates that the
power transmission from the motor to the load is interrupted. For pumps, insufficient torque can
indicate a leakage or dry-running.
The converter monitors the torque based on the envelope curve depending on the speed
against a lower and upper torque.
6SHHG>USP@
SVSHHGWKUHVKROG
6SHHGWKUHVKROGS
6SHHGWKUHVKROGS
SPD[LPXPVSHHG
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGXSSHUS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGXSSHUS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGXSSHUS
7RUTXH>1P@
If the torque lies in the impermissible range longer than time p2192, the converter reacts as
specified in p2181.
The monitoring is not active below speed threshold 1 and above speed threshold 3.
Parameters
Number
Name
Factory setting
p2181[D]
Load monitoring, response
0
p2182[D]
Load monitoring, speed threshold 1
150 rpm
p2183[D]
Load monitoring, speed threshold 2
900 rpm
p2184[D]
Load monitoring, speed threshold 3
1500 rpm
p2185[D]
Load monitoring, torque threshold 1, upper
10000000 Nm
p2186[D]
Load monitoring torque threshold 1, lower
0 Nm
p2187[D]
Load monitoring torque threshold 2, upper
10000000 Nm
p2188[D]
Load monitoring torque threshold 2, lower
0 Nm
p2189[D]
Load monitoring torque threshold 3, upper
10000000 Nm
p2190[D]
Load monitoring torque threshold 3, lower
0 Nm
p2191[D]
Load monitoring torque threshold, no load
0 Nm
p2192[D]
Load monitoring, delay time
10 s
p2193[D]
Load monitoring configuration
1
Advanced commissioning
6.7 Drive protection
SINAMICS G120XA converter
314
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......