
6.7.6.3
Blocking protection
Function description
If the mechanical load is too high, the motor may block. For a blocked motor, the motor current
corresponds to the set current limit without the speed reaching the specified setpoint.
If the speed lies below the speed threshold p2175 for the time p2177 while the motor current
reaches the current limit, the converter signals "Motor blocked" and fault F07900.
Parameters
Number
Name
Factory settings
p0045
Display values of smoothing time constant
4 ms
r0063
CO: Speed actual value
- rpm
p2175[D]
Motor blocked speed threshold
120 rpm
p2177[D]
Motor blocked delay time
3 s
r2198
Status word monitoring functions 2
-
Advanced commissioning
6.7 Drive protection
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
313
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......