Control optimization required
In some cases, the self optimization result is not satisfactory, or self optimization is not possible
as the motor cannot freely rotate.
W
Initially, the speed actual value follows the speed setpoint with
some delay, and then overshoots the speed setpoint.
W
First, the actual speed value increases faster than the speed
setpoint. Before the setpoint reaches its final value, it passes
the actual value. Finally, the actual value approaches the set‐
point without any significant overshoot.
In the two cases describe above, we recommend that you manually optimize the speed control.
Optimizing the speed controller
Requirements
● Torque precontrol is active: p1496 = 100 %.
● The load moment of inertia is constant and independent of the speed.
● The converter requires 10 % … 50 % of the rated torque to accelerate.
When necessary, adapt the ramp-up and ramp-down times of the ramp-function generator
(p1120 and p1121).
Procedure
1. Switch on the motor.
2. Enter a speed setpoint of approximately 40 % of the rated speed.
3. Wait until the actual speed has stabilized.
4. Increase the setpoint up to a maximum of 60% of the rated speed.
5. Monitor the associated characteristic of the setpoint and actual speed.
6. Optimize the controller by adapting the ratio of the moments of inertia of the load and motor
(p0342):
W
Initially, the speed actual value follows the speed setpoint with
some delay, and then overshoots the speed setpoint.
● Increase p0342
W
Initially, the speed actual value increases faster than the speed
setpoint. The setpoint passes the actual value before reaching its
final value. Finally, the actual value approaches the setpoint with‐
out any overshoot.
● Reduce p0342
7. Switch off the motor.
Advanced commissioning
6.6 Motor control
SINAMICS G120XA converter
294
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......