6.4.2.2
Invert setpoint
Function description
S
[
\
[
\
W
\
\
[
[
The function inverts the sign of the setpoint using a binary signal.
Example
To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal
of your choice.
Table 6-47
Application examples showing how a setpoint is inverted
Parameter
Description
p1113 = 722.1
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Converter inverts the setpoint.
p1113 = 2090.11
Inverts the setpoint via the fieldbus (control word 1, bit 11).
Parameter
Number
Name
Factory setting
p1113[C]
BI: Setpoint inversion
Dependent on the
converter
Advanced commissioning
6.4 Setpoints and setpoint processing
SINAMICS G120XA converter
236
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB