● IND, bit 0 … 7 (page index): = 90 hex (offset 6000 corresponds to 90 hex)
● Because you want to read the parameter value, words 3 and 4 in the parameter channel for
requesting the parameter value are irrelevant. They should be assigned a value of 0, for
example.
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG
3:(ORZWKZRUG
,1'QGZRUG
3DJHLQGH[
3DUDPHWHUQXPEHU
6XELQGH[
3DUDPHWHUYDOXH
3.(VWZRUG
'ULYHREMHFW
,QGH[
$.
Figure 6-13
Telegram for a read request from p7841[2]
Parameter number
Parameter numbers < 2000
PNU = parameter number.
Write the parameter number into the PNU (PKE bit 10 ... 0).
Parameter numbers ≥ 2000
PNU = parameter number - offset.
Write the parameter number minus the offset into the PNU
(PKE bit 10 … 0).
Write the offset in the page index (IND bit 15 … 8).
Table 6-38
Offset and page index of the parameter numbers
Parameter number Offset Page index
Hex
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
0000 … 1999
0
0 hex
0
0
0
0
0
0
0
0
2000 … 3999
2000
80 hex
1
0
0
0
0
0
0
0
6000 … 7999
6000
90 hex
1
0
0
1
0
0
0
0
8000 … 9999
8000
20 hex
0
0
1
0
0
0
0
0
10000 … 11999
10000 A0 hex
1
0
1
0
0
0
0
0
20000 … 21999
20000 50 hex
0
1
0
1
0
0
0
0
30000 … 31999
30000 F0 hex
1
1
1
1
0
0
0
0
60000 … 61999
60000 74 hex
0
1
1
1
0
1
0
0
Indexed parameters
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 7 … 0).
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
178
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......