r11094
CO: Free tec_ctrl 0 output signal / Ftec0 out_sig
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Display and connector output for the output signal of the free technology controller 0.
p11097
CI: Free tec_ctrl 0 limit maximum signal source / Ftec0 lim max s_s
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
11091[0]
Description:
Sets the signal source for the maximum limit of the free technology controller 0.
Dependency:
See also: p11091
p11098
CI: Free tec_ctrl 0 limit minimum signal source / Ftec0 lim min s_s
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
11092[0]
Description:
Sets the signal source for the minimum limit of the free technology controller 0.
Dependency:
See also: p11092
p11099
CI: Free tec_ctrl 0 limit offset signal source / Ftec0 lim offs
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the limit offset of the free technology controller 0.
p11100
BI: Free tec_ctrl 1 enable / Ftec1 enab
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to switch in/switch out the free technology controller 1.
1 signal: The technology controller is switched in.
0 signal: The technology controller is switched out.
Parameters
7.2 Parameter list
SINAMICS G120X converter
900
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......