Description:
Compound braking current is used to define the amount of DC current that is produced on stopping the motor during
U/f operation to further increase the DC braking function.
Compound braking is a superimposition of the DC braking function with regenerative braking (net braking along the
ramp) after OFF1 or OFF3. This permits braking with controlled motor frequency and minimum power input into the
motor.
Effective braking without using additional hardware components is obtained by optimizing the ramp down time and
compound braking.
Dependency:
The compound braking current is only activated if the DC link voltage exceeds the threshold value in r1282.
Compound braking does not operate in the following cases:
- DC braking activated (p1230, r1239).
- motor is still not magnetized (e.g. for flying restart).
- vector control parameterized (p1300 >= 20).
- synchronous motor used (p0300 = 2xx).
NOTICE
Generally, increasing the braking current improves the braking effect when stopping the motor. However, if the value
is set too high, then the drive can be tripped (shut down) as a result of overcurrent or ground fault.
Recommendation: p3856 < 100 % x (r0209 - r0331) / p0305 / 2
Compound braking generates a current in the motor with a ripple manifesting the rotational frequency. The higher the
braking current is set, the higher the resulting ripple, especially when the Vdc_max control is simultaneously active
(refer to p1280).
Note
The parameter value is entered relative to the rated motor current (p0305).
Compound braking is deactivated with p3856 = 0%.
p3857[0...n]
DC quantity controller P gain / DC_ctrl Kp
Access level: 3
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6797
Min:
0.000
Max:
100000.000
Factory setting:
0.000
Description:
Sets the proportional gain of the DC quantity controller for the overmodulation range.
p3858[0...n]
DC quantity controller integral time / DC_ctrl Tn
Access level: 3
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6797
Min:
0.00 [ms]
Max:
1000.00 [ms]
Factory setting:
2.00 [ms]
Description:
Sets the integral time for the DC quantity controller.
r3859.0...1
CO/BO: Compound braking/DC quantity control status word / Comp-br/DC_ctr ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6797
Min:
-
Max:
-
Factory setting:
-
Description:
Display and connector output for the status word of the compound braking and DC quantity control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Compound braking active
Yes
No
-
01
DC quantity control active in the overmodulation range
Yes
No
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
842
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......