p2207[0...n]
CO: Technology controller fixed value 7 / Tec_ctr fix val 7
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: 7950
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
70.00 [%]
Description:
Sets the value for fixed value 7 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2208[0...n]
CO: Technology controller fixed value 8 / Tec_ctr fix val 8
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: 7950
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
80.00 [%]
Description:
Sets the value for fixed value 8 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2209[0...n]
CO: Technology controller fixed value 9 / Tec_ctr fix val 9
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: 7950
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
90.00 [%]
Description:
Sets the value for fixed value 9 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2210[0...n]
CO: Technology controller fixed value 10 / Tec_ctr fix val 10
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: 7950
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the value for fixed value 10 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
793
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......