12
External alarm 3 (A07852) effective
Yes
No
8065
13
External fault 1 (F07860) effective
Yes
No
8060
14
External fault 2 (F07861) effective
Yes
No
8060
15
External fault 3 (F07862) effective
Yes
No
8060
Dependency:
See also: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
r2139.0...15
CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2548
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for status word 1 of faults and alarms.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Being acknowledged
Yes
No
-
01
Acknowledgment required
Yes
No
-
03
Fault present
Yes
No
8060
06
Internal message 1 present
Yes
No
-
07
Alarm present
Yes
No
8065
08
Internal message 2 present
Yes
No
-
11
Alarm class bit 0
High
Low
-
12
Alarm class bit 1
High
Low
-
13
Maintenance required
Yes
No
-
14
Maintenance urgently required
Yes
No
-
15
Fault gone/can be acknowledged
Yes
No
-
Note
For bit 03, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present" or "alarm present" has occurred, a change
in the buffer was also detected (r0944, r9744, r2121).
For bit 06, 08:
These status bits are used for internal diagnostic purposes only.
For bits 11, 12:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes only
on certain automation systems with integrated SINAMICS functionality.
p2140[0...n]
Hysteresis speed 2 / n_hysteresis 2
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8010
Min:
0.00 [rpm]
Max:
300.00 [rpm]
Factory setting:
90.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
See also: p2155, r2197
Parameters
7.2 Parameter list
SINAMICS G120X converter
776
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......