p1461[0...n]
Speed controller Kp adaptation speed upper scaling / n_ctr Kp n up scal
Access level: 3
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6050
Min:
0.0 [%]
Max:
200000.0 [%]
Factory setting:
100.0 [%]
Description:
Sets the P gain of the speed controller for the upper adaptation speed range (> p1465).
The entry is made referred to the P gain for the lower adaptation speed range of the speed controller (% referred to
p1470).
Dependency:
See also: p1464, p1465
Note
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition
p1464, then the controller gain below p1465 is adapted with p1461. This means that an adaptation can be implemented
for low speeds without having to change the controller parameters.
p1463[0...n]
Speed controller Tn adaptation speed upper scaling / n_ctr Tn n up scal
Access level: 3
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6050
Min:
0.0 [%]
Max:
200000.0 [%]
Factory setting:
100.0 [%]
Description:
Sets the integral time of the speed controller after the adaptation speed range (> p1465).
The entry is made referred to the integral time for the lower adaptation speed range of the speed controller (% referred
to p1472).
Dependency:
See also: p1464, p1465
Note
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition point
p1464, then the controller integral time below p1465 is adapted with p1463. This means that an adaptation can be
implemented for low speeds without having to change the controller parameters.
p1464[0...n]
Speed controller adaptation speed lower / n_ctrl n lower
Access level: 3
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 6050
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
0.00 [rpm]
Description:
Sets the lower adaptation speed of the speed controller.
No adaptation is effective below this speed.
Dependency:
See also: p1461, p1463, p1465
Note
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition point
p1464, then the controller below p1465 is adapted with p1461 or p1463. This means that an adaptation can be
implemented for low speeds without having to change the controller parameters.
p1465[0...n]
Speed controller adaptation speed upper / n_ctrl n upper
Access level: 3
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 6050
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
210000.00 [rpm]
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
681
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......