If condensation or conductive pollution can be excluded at the installation site, a lower degree
of control cabinet protection may be permitted.
Mounting position
Figure 3-6
Only mount in the vertical position with the line connection at the bottom
3.4.2
Dimension drawings and drill patterns
Overview
The converters are designed to be mounted in accordance with the dimension drawings, in a
cabinet using screws, nuts and washers.
Note
To comply with EMC specifications, it is recommended to mount the converter on an electrically
conductive mounting panel in the cabinet. This mounting panel should be connected to the
cabinet PE.
Mounting
3.4 Mounting the converter
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
61