r0963
PROFIBUS baud rate / PB baud rate
G120X_DP
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
255
Factory setting:
-
Description:
Displays the corresponding value for the PROFIBUS baud rate.
Value:
0:
9.6 kbit/s
1:
19.2 kbit/s
2:
93.75 kbit/s
3:
187.5 kbit/s
4:
500 kbit/s
6:
1.5 Mbit/s
7:
3 Mbit/s
8:
6 Mbit/s
9:
12 Mbit/s
10:
31.25 kbit/s
11:
45.45 kbit/s
255:
Unknown
r0964[0...6]
Device identification / Device ident
G120X_DP
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the device identification.
Index:
[0] = Company (Siemens = 42)
[1] = Device type
[2] = Firmware version
[3] = Firmware date (year)
[4] = Firmware date (day/month)
[5] = Number of drive objects
[6] = Firmware patch/hot fix
Note
Example:
r0964[0] = 42 --> SIEMENS
r0964[1] = device type, see below
r0964[2] = 403 --> first part of the firmware version V04.03 (for second part, refer to index 6)
r0964[3] = 2010 --> year 2010
r0964[4] = 1705 --> 17th of May
r0964[5] = 2 --> 2 drive objects
r0964[6] = 200 --> second part, firmware version (complete version: V04.03.02.00)
Device type:
r0964[1] = 5720 --> SINAMICS G120X DP
Parameters
7.2 Parameter list
SINAMICS G120X converter
600
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......