p0870
BI: Close main contactor / Close main cont
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to close the main contactor.
Note
The main contactor is also closed when the converter is switched on after issuing the necessary enable signals. A
binector input p0870 = 1 signal prevents the main contactor from being opened when enable signals are withdrawn.
r0898.0...10
CO/BO: Control word sequence control / STW seq_ctrl
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2501
Min:
-
Max:
-
Factory setting:
-
Description:
Display and connector output for the control word of the sequence control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Enable operation
Yes
No
-
04
Enable ramp-function generator
Yes
No
-
05
Continue ramp-function generator
Yes
No
-
06
Enable speed setpoint
Yes
No
-
08
Jog 1
Yes
No
3001
09
Jog 2
Yes
No
3001
10
Master control by PLC
Yes
No
-
Note
OC: Operating condition
r0899.0...11
CO/BO: Status word sequence control / ZSW seq_ctrl
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2503
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the status word of the sequence control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ready for switching on
Yes
No
-
01
Ready
Yes
No
-
02
Operation enabled
Yes
No
-
03
Jog active
Yes
No
-
04
No coasting active
OFF2 inactive
OFF2 active
-
05
No Quick Stop active
OFF3 inactive
OFF3 active
-
06
Switching on inhibited active
Yes
No
-
07
Drive ready
Yes
No
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
596
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......