05
Use voltage measured values for flying restart
Yes
No
-
07
Voltage calibration when switching on
Yes
No
-
08
Voltage monitoring when switching on
Yes
No
-
09
Voltage monitoring cyclic
Yes
No
-
Note
The motor data identification must be executed when using the voltage measurement.
p0251[0...n]
Operating hours counter power unit fan / PU fan t_oper
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [h]
Max:
4294967295 [h]
Factory setting:
0 [h]
Description:
Displays the power unit fan operating hours.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency:
See also: p0252
See also: A30042
Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
p0252
Maximum operating time power unit fan / PU fan t_oper max
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 4
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [h]
Max:
100000 [h]
Factory setting:
40000 [h]
Description:
Sets the maximum operating time of the power unit fan.
The prealarm (warning) is output 500 hours before this set value.
The monitoring is deactivated with p0252 = 0.
Dependency:
See also: p0251
See also: A30042
Note
For PM330 power units, the maximum operating time of the fan on the power unit is saved and displayed in p0252. The
"Restore factory setting" function or a project download does not influence p0252. Users can manually change the
maximum operating time of the fan. The modified value is also saved to the power unit.
p0254[0...n]
Operating hours counter power unit fan inside the converter / PU inner fan t_op
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [h]
Max:
4294967295 [h]
Factory setting:
0 [h]
Description:
Displays the power unit fan operating hours of the internal fan in the power unit.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency:
See also: A30042
Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
Parameters
7.2 Parameter list
SINAMICS G120X converter
508
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......