r0076
CO: Current actual value field-generating / Id_act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 5700, 5714,
5730, 6700, 6714, 6799
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Display and connector output for the field-generating current actual value (Id_act).
Dependency:
See also: r0029
Note
This value is irrelevant for the U/f control mode.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
r0077
CO: Current setpoint torque-generating / Iq_set
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 6700, 6710
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Display and connector output for the torque-generating current setpoint.
Note
This value is irrelevant for the U/f control mode.
r0078
CO: Current actual value torque-generating / Iq_act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 6310, 6700,
6714, 6799
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Display and connector output for the torque-generating current actual value (Iq_act).
Dependency:
See also: r0030
Note
This value is irrelevant for the U/f control mode.
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
r0079
CO: Torque setpoint / M_set
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2003
Dynamic index: -
Unit group: 7_1
Unit selection: p0505
Function diagram: 6020, 6060,
6710
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description:
Display and connector output for the torque setpoint at the output of the speed controller.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
495
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......